Assessment of bioaerosol reduction methods in stem cell transplant units at a University Hospital

dc.contributor.author

Alderman, TS

dc.contributor.author

Thomann, WR

dc.contributor.author

Hunt, DL

dc.date.accessioned

2022-08-04T17:27:15Z

dc.date.available

2022-08-04T17:27:15Z

dc.date.issued

2004-12-01

dc.date.updated

2022-08-04T17:27:14Z

dc.description.abstract

Severely immunocompromised patients, such as those who have undergone stem cell transplantation, must be housed in a protective environment to reduce the risk of acquiring health care-associated fungal infections. This 11-month study was conducted at Duke University Hospital to evaluate the efficacy of the existing engineering controls (EC) for two such protective units: the pediatric stem cell transplant unit (PTU) and the adult stem cell transplant unit (ATU). In addition, a standard intensive care unit (ICU) was included as a "control" nursing unit. The engineering controls evaluated during the study included high-efficiency particulate air (HEPA) filtration of supply air, supplemental HEPA refiltration, air change rates, directional airflow in patient rooms, positive pressure gradient (directional air flows) throughout the unit, and an interlocked airlock. Significant performance differences were identified when the bioaerosol sampling data from the three units were compared. These differences were found related to the presence and performance of the evaluated engineering controls. The concentration of airborne fungal spores in the PTU, which was equipped with all of the evaluated engineering controls performing at design specification, was found less than both the ATU (p = 0.0007) and the ICU (p = 0.001). This suggests that utilizing an appropriate combination of engineering control measures is an effective means of controlling airborne bioburden. This study also provides evidence of the importance of supplemental HEPA refiltration and the establishment and maintenance of a strong positive pressure gradient (>2.5 pascals). © 2004 ASHRAE.

dc.identifier.issn

2166-4870

dc.identifier.issn

2166-4870

dc.identifier.uri

https://hdl.handle.net/10161/25579

dc.relation.ispartof

IAQ Conference

dc.title

Assessment of bioaerosol reduction methods in stem cell transplant units at a University Hospital

dc.type

Journal article

pubs.organisational-group

Duke

pubs.organisational-group

School of Medicine

pubs.organisational-group

Faculty

pubs.organisational-group

Staff

pubs.organisational-group

Clinical Science Departments

pubs.organisational-group

Family Medicine and Community Health

pubs.organisational-group

Medicine

pubs.organisational-group

Family Medicine & Community Health,Occupational & Environmental Medicine

pubs.organisational-group

Medicine, Duke Human Vaccine Institute

pubs.publication-status

Published

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
153567600400900304.pdf
Size:
187.33 KB
Format:
Adobe Portable Document Format
Description:
Published version